- 7M.24 single-phase energy meter (Modbus RS485)
Energy meter · Modbus register map
Finder 7M.24 single-phase energy meter (Modbus RS485) Modbus register map
Updated 17 November 2026
The 7M.24 is Finder's single-phase MID energy meter for DIN rail. The RS485 version answers Modbus RTU and offers its measurements both in packed integer formats and as IEEE 754 floats. This map uses the float block (voltage, current, powers, power factor, THD, frequency, energy counters) plus identification, status, tariff, reset and serial-port registers.
This page lists 60 Modbus registers for the Finder 7M.24 single-phase energy meter (Modbus RS485) — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Finder’s own free documentation (linked below) and checked against it.
- Manufacturer
- Finder
- Model
- 7M.24 single-phase energy meter (Modbus RS485)
- Equipment type
- Energy meter
- Registers
- 60 (11 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- 7M.24, 7M24, Finder 7M24 Modbus
Integration notes: Finder 7M.24 single-phase energy meter (Modbus RS485)
Read input registers with function 04 and decode the float block high word first: subtract 30000 from the printed number (U1 at 32500 is wire 2500). Energy comes as floats in Wh/varh from 32752.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 2500 | U1 | FLOAT32 ABCD | U1 voltage | Read |
| IR 2516 | I1 | FLOAT32 ABCD | I1 current | Read |
| IR 2490 | Active power total (Pt) | FLOAT32 ABCD | Total active power | Read |
| IR 2496 | Power factor total (PFt) | FLOAT32 ABCD | Total power factor | Read |
| IR 2498 | Frequency | FLOAT32 ABCD | Frequency | Read |
| IR 2752 | Energy counter n1 | FLOAT32 ABCD | Energy counter n1 (Wh) | Read |
Enable Modbus control & writes
Modbus RTU runs on the RS485 versions. Port 1 address, baud, stop bits and parity are holding registers 40202-40205; raise the access level with the user password at 40001 first, then save with 40012 = 1.
Byte order & addressing
- The memory reference is 30000/40000: printed 30107 is wire address 107.
- Floats and 32-bit integers are high word first (ABCD).
Network setup
- Modbus address 1-247; 8 data bits only; parity none/odd/even; 1 or 2 stop bits.
Watch out for
- Which counter is import or export depends on the counter configuration registers; verify against the display.
- Read 30099 for the largest register count the meter accepts per request.
Finder 7M.24 single-phase energy meter (Modbus RS485) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 1doc 30001 | Model number | 16-character text, two characters per register. | STRING[16] | Read | ||||
| IR | 9doc 30009 | Serial number | 8-character text. | STRING[8] | Read | ||||
| IR | 13doc 30013 | Software version | UINT16 | Read | |||||
| IR | 44doc 30044 | Status register | BITMAP16 | Read | bit 0 = Locked; bit 4 = Clock not set | ||||
| IR | 76doc 30076 | MID lock status | UINT16 | Read | 0 = Unlocked; 1 = Locked | ||||
| IR | 99doc 30099 | Modbus max registers per read | Largest register count the meter accepts in one read. | UINT16 | Read | ||||
| IR | 101doc 30101 | Phase valid measurement | BITMAP16 | Read | bit 0 = Invalid measurement phase 1 | ||||
| IR | 103doc 30103 | Run time | INT32 | ABCD | s | Read | |||
| IR | 197doc 30197 | External relay status | UINT16 | Read | 0 = Off; 1 = On; 250 = Comm. error; 255 = Not connected | ||||
| IR | 400doc 30400 | Checksum status | 0 = no error. | BITMAP16 | Read | bit 0 = Parameter CRC error; bit 1 = Firmware CRC error; bit 2 = MID-lock error; bit 6 = Measurement module checksum error; bit 7 = Software checksum error; bit 8 = Calibration data checksum error; bit 9 = MID setting data checksum error; bit 10 = Setting data checksum error | |||
| IR | 405doc 30405 | Current active tariff | UINT16 | Read | |||||
| IR | 2480doc 32480 | Run time (float) | FLOAT32 | ABCD | s | Read | |||
| IR | 2484doc 32484 | Uavg phase-to-neutral | FLOAT32 | ABCD | V | Read | |||
| IR | 2488doc 32488 | Sum of currents | FLOAT32 | ABCD | A | Read | |||
| IR | 2490doc 32490 | Active power total (Pt) | FLOAT32 | ABCD | W | Read | |||
| IR | 2492doc 32492 | Reactive power total (Qt) | FLOAT32 | ABCD | var | Read | |||
| IR | 2494doc 32494 | Apparent power total (St) | FLOAT32 | ABCD | VA | Read | |||
| IR | 2496doc 32496 | Power factor total (PFt) | FLOAT32 | ABCD | Read | ||||
| IR | 2498doc 32498 | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| IR | 2500doc 32500 | U1 | FLOAT32 | ABCD | V | Read | |||
| IR | 2516doc 32516 | I1 | FLOAT32 | ABCD | A | Read | |||
| IR | 2530doc 32530 | Active power L1 (P1) | FLOAT32 | ABCD | W | Read | |||
| IR | 2538doc 32538 | Reactive power L1 (Q1) | FLOAT32 | ABCD | var | Read | |||
| IR | 2546doc 32546 | Apparent power L1 (S1) | FLOAT32 | ABCD | VA | Read | |||
| IR | 2554doc 32554 | Power factor L1 (PF1) | FLOAT32 | ABCD | Read | ||||
| IR | 2570doc 32570 | Angle U1-I1 | FLOAT32 | ABCD | ° | Read | |||
| IR | 2576doc 32576 | Power angle total (atan2(Pt,Qt)) | FLOAT32 | ABCD | ° | Read | |||
| IR | 2588doc 32588 | I1 THD | FLOAT32 | ABCD | % | Read | |||
| IR | 2594doc 32594 | U1 THD | FLOAT32 | ABCD | % | Read | |||
| IR | 2658doc 32658 | Internal temperature | FLOAT32 | ABCD | °C | Read | |||
| IR | 2750doc 32750 | Active tariff (float) | FLOAT32 | ABCD | Read | ||||
| IR | 2752doc 32752 | Energy counter n1 | Non-resettable counter. | FLOAT32 | ABCD | Wh | Read | ||
| IR | 2754doc 32754 | Energy counter n2 | Non-resettable counter. | FLOAT32 | ABCD | varh | Read | ||
| IR | 2756doc 32756 | Energy counter n3 | Non-resettable counter. | FLOAT32 | ABCD | Wh | Read | ||
| IR | 2758doc 32758 | Energy counter n4 | Non-resettable counter. | FLOAT32 | ABCD | varh | Read | ||
| IR | 2760doc 32760 | Energy counter 1 | Resettable user counter; Wh, varh or VAh per its parameter. | FLOAT32 | ABCD | Read | |||
| IR | 2762doc 32762 | Energy counter 2 | Resettable user counter; Wh, varh or VAh per its parameter. | FLOAT32 | ABCD | Read | |||
| IR | 2764doc 32764 | Energy counter 3 | Resettable user counter; Wh, varh or VAh per its parameter. | FLOAT32 | ABCD | Read | |||
| IR | 2766doc 32766 | Energy counter 4 | Resettable user counter; Wh, varh or VAh per its parameter. | FLOAT32 | ABCD | Read | |||
| IR | 2768doc 32768 | Energy counter 5 | Resettable user counter; Wh, varh or VAh per its parameter. | FLOAT32 | ABCD | Read | |||
| IR | 2770doc 32770 | Energy counter 6 | Resettable user counter; Wh, varh or VAh per its parameter. | FLOAT32 | ABCD | Read | |||
| IR | 2772doc 32772 | Energy counter 7 | Resettable user counter; Wh, varh or VAh per its parameter. | FLOAT32 | ABCD | Read | |||
| IR | 2774doc 32774 | Energy counter 8 | Resettable user counter; Wh, varh or VAh per its parameter. | FLOAT32 | ABCD | Read | |||
| IR | 2985doc 32985 | Nominal phase voltage | FLOAT32 | ABCD | V | Read | |||
| IR | 2987doc 32987 | Nominal phase current | FLOAT32 | ABCD | A | Read | |||
| IR | 2989doc 32989 | Nominal phase power | FLOAT32 | ABCD | W | Read | |||
| IR | 2991doc 32991 | Nominal total power | FLOAT32 | ABCD | W | Read | |||
| IR | 2993doc 32993 | Nominal total current | FLOAT32 | ABCD | A | Read | |||
| IR | 2995doc 32995 | Nominal frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 10doc 40010 | Active access level | 0 = full protection. | UINT16 | Read/write | ||||
| HR | 12doc 40012 | Operator command | UINT16 | Write | 1 = Save settings; 2 = Abort settings; 3 = Restart instrument | ||||
| HR | 15doc 40015 | IR external relay command | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 30doc 40030 | Select active tariff | Tariff 1 to 6. | UINT16 | Read/write | ||||
| HR | 31doc 40031 | Reset energy counters | Set a bit to reset that resettable counter. | BITMAP16 | Write | bit 0 = Reset counter 1; bit 1 = Reset counter 2; bit 2 = Reset counter 3; bit 3 = Reset counter 4; bit 4 = Reset counter 5; bit 5 = Reset counter 6; bit 6 = Reset counter 7; bit 7 = Reset counter 8 | |||
| HR | 202doc 40202 | Port 1 Modbus address | 1 to 247. | UINT16 | Read/write | ||||
| HR | 203doc 40203 | Port 1 baud rate | UINT16 | Read/write | 0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400; 6 = 57600; 7 = 115200 | ||||
| HR | 204doc 40204 | Port 1 stop bits | UINT16 | Read/write | 0 = 1 stop bit; 1 = 2 stop bits | ||||
| HR | 205doc 40205 | Port 1 parity | UINT16 | Read/write | 0 = None; 1 = Odd; 2 = Even | ||||
| HR | 421doc 40421 | Energy counter n1 parameter | Quantity this counter integrates. | UINT16 | Read/write | 0 = No parameter; 1 = Active power; 2 = Reactive power; 3 = Apparent power; 5 = Active power phase 1; 6 = Reactive power phase 1; 7 = Apparent power phase 1 | |||
| HR | 422doc 40422 | Energy counter n1 configuration | Which quadrants are counted; decides import vs export. | BITMAP16 | Read/write | bit 0 = Quadrant I enabled; bit 1 = Quadrant II enabled; bit 2 = Quadrant III enabled; bit 3 = Quadrant IV enabled; bit 4 = Absolute value; bit 5 = Invert value |
Notes on this map
- Wire address = printed number - 30000 (input) or - 40000 (holding); see the 30107 / 0x006B example.
- T_float is IEEE 754 single precision, high word first (ABCD); the data-type page's example stores 123.45 as 42F6 E666. T3 (signed 32-bit) is also high word first.
- Left out: the integer measurement block (T5/T6/T7 packed exponent formats), the mantissa/exponent energy counters and the '1000 x energy counter' block, as for the 7M.38 map.
- Left out: duplicate float rows (a second Pt/Qt/St/PFt/frequency set at 32536-32584 and float counters n1-n4 at 32638-32645 without a function code), CAP/IND power factor floats (sign convention not explained), and the alarm, logic, LCD, data-logger and other configuration groups.
- Energy counters 1-8 are user counters reset through 40031; what each one integrates is set in its parameter/configuration registers (40421 onward), so check the assignment on the meter.
- Writing settings needs the access level raised by writing the user password to 40001-40002 (function 16), then saving with operator command 40012 = 1.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Finder 7M.24 single-phase energy meter (Modbus RS485)
What Modbus registers does the Finder 7M.24 single-phase energy meter (Modbus RS485) have?
This map lists 60 registers: 49 input registers, 11 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Finder 7M.24 single-phase energy meter (Modbus RS485) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as 3xxxx (input, function 04) and 4xxxx (holding, functions 03/06/16) with 30000 / 40000 as the memory reference, not 30001. The document's request example reads U1 (30107) by sending start address 0x006B = 107. Wire address = printed number minus 30000 or 40000: Pt float 32490 is input register 2490.
What byte order does the Finder 7M.24 single-phase energy meter (Modbus RS485) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Finder 7M.24 single-phase energy meter (Modbus RS485)?
Start with IR 2500 U1 (U1 voltage); IR 2516 I1 (I1 current); IR 2490 Active power total (Pt) (Total active power); IR 2496 Power factor total (PFt) (Total power factor); IR 2498 Frequency (Frequency); IR 2752 Energy counter n1 (Energy counter n1 (Wh)).
How do I enable Modbus control of the Finder 7M.24 single-phase energy meter (Modbus RS485)?
Modbus RTU runs on the RS485 versions. Port 1 address, baud, stop bits and parity are holding registers 40202-40205; raise the access level with the user password at 40001 first, then save with 40012 = 1.
Where is the official Finder 7M.24 single-phase energy meter (Modbus RS485) Modbus documentation?
The source is Modbus Communication Protocol 7M24 - 7M38 (v2), revision 2021-06-30, published free by Finder at https://cdn.findernet.com/app/uploads/Modbus-7M24-7M38_v2_30062021.pdf.
More Finder Modbus register maps
Other power & energy meters register maps
- Power meter
IME Nemo 96HD multifunction meter (MF96001 / MF96021)
IME Nemo 96HD panel meters MF96001 and MF96021 with an RS-485 module, per protocol PR106 (software 3.18).
Also known as: MF96001, MF96021, Nemo 96HD - Energy meter
inepro Metering PRO1 single-phase energy meter (2026 PRO line)
PRO1-Mod (art. 1101) and PRO1-Mod-Ba (art. 1102, with RTC tariffs) from the 2026 PRO1 user manual version 1.3; the PRO1-S has no Modbus.
Also known as: PRO1-Mod, PRO1-Mod-Ba, PRO1 1U AC 45A Mo T MID, PRO1 1U AC 45A Mo T Ba MID, 1101, 1102 - Power meter (power analyser)
Janitza UMG 104 power analyser (RS-485 Modbus RTU)
UMG 104 DIN-rail power analyser, firmware 1.268, per address list 1.041.006.1.e (01/2023).
Also known as: UMG104, UMG 104, Janitza UMG104 - Power meter (power quality analyser)
Janitza UMG 604-PRO power analyser (Modbus RTU / Modbus TCP)
UMG 604-PRO from firmware release 5.028, per address list 1.033.034.e (08/2023).
Also known as: UMG604-PRO, UMG 604PRO, UMG604PRO, UMG 604-EP PRO, Janitza UMG 604 - Power meter (power quality analyser)
KMB systems SMC / SMY / SMZ / ARTIQ power analysers (Modbus manual v4.0)
KMB systems panel and DIN-rail meters and analysers with firmware 4.x, per 'Modbus-TCP and Modbus-RTU protocol documentation' (revision of January 19, 2023). Which blocks a model supports depends on the instrument and its firmware modules.
Also known as: SMC 133, SMC 144, PA 144, SML 133, SMM 133, SMC 118, SMY 133, SMY 134, SMP 133, SMZ 133, SMC 235, SMC 233, ARTIQ 235, ARTIQ 233, BC 235, BCPM 233, EMU 3, SMZ 244 - Pump (chemical metering pump)
LMI Excel XR series electronic metering pump (Modbus RTU)
LMI Excel XR electronic metering pumps fitted with the Modbus RTU interface (manual 55312 rev 04).
Also known as: Excel XR, LMI Excel XR, Milton Roy Excel XR, Excel XR Modbus
All power & energy meters Modbus register maps →
Source: Modbus Communication Protocol 7M24 - 7M38 · v2 · rev. 2021-06-30. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.