Sensor (gas transmitter / gas detector) · Modbus register map

Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface Modbus register map

Updated 17 November 2026

Short answer

ATI's D12 (explosion-proof) and F12 (NEMA 4X) gas transmitters can carry a Modbus RTU option on RS-232 or RS-485. Everything sits in holding registers: a block at 40033-40052 gives fault and status words, gas concentration, temperature and loop current, and settings or calibrations are run by loading parameters and writing a subroutine number to 40001.

This page lists 29 Modbus registers for the Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Analytical Technology (ATI)’s own free documentation (linked below) and checked against it.

Manufacturer
Analytical Technology (ATI)
Model
D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface
Equipment type
Sensor (gas transmitter / gas detector)
Registers
29 (14 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Also known as
D12, F12, D12 gas transmitter, F12 gas transmitter
Source document
D12/F12 Series Modbus Interface O&M Manual · Rev G · rev. 2007-08 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface

Integration in brief

Read holding registers 40035-40048 (address 34, 14 registers) in one FC03 request: faults, status, concentration, %FS, temperature and blanked readings, with floats low word first. Use subroutine 31 (with the alarm bits in 40003) to reset latched alarms.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 34FaultsBITMAP16Fault bitsRead
HR 35StatusBITMAP16Status bits (caution/warning/alarm/fault)Read
HR 42Gas concentration (blanked)FLOAT32 CDABGas concentration (blanked)Read
HR 38Concentration % of full scaleFLOAT32 CDABConcentration % full scaleRead
HR 40TemperatureFLOAT32 CDABTemperatureRead
HR 46Current loop outputFLOAT32 CDABLoop currentRead

Enable Modbus control & writes

Modbus is a factory-installed option. Set slave address on the transmitter at Menu > Setup > Modbus and baud/parity at Menu > Setup > System > Commun.

Byte order & addressing

Network setup

Watch out for

Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

29 of 29 shown
Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Subroutine selectWrite a subroutine number to run it, after loading parameters into 40003-40006.UINT16Read/write10 = Zero sensor; 11 = Span sensor; 12 = Get calibration history info; 13 = Get calibration record; 14 = Change sensor range; 15 = Change sensor damping; 16 = Change sensor blanking; 17 = Change autotest state; 18 = Calibrate temperature reading; 20 = Change alarm set point; 21 = Change alarm reset point; 22 = Change alarm set delay; 23 = Change alarm reset delay; 27 = Change alarm options; 28 = Change relay configuration; 29 = Change inhibit timeout period; 30 = Change alarm inhibit state; 31 = Reset alarms; 32 = Start alarm relay test; 33 = Stop alarm relay test; 40 = Change inhibit mA level; 41 = Change fault mA level; 42 = Change autotest mA level; 47 = Force mA output; 48 = Correct 4 mA level; 49 = Correct 20 mA level; 50 = Change lock status; 51 = Change password; 60 = Change system clock; 61 = Input keycode; 70 = Change datalog state; 71 = Change datalog sampling rate; 72 = Get datalog info; 73 = Get datalog record; 100 = Convert concentration real to %FS integer; 101 = Convert %FS integer to real
HR1doc 40002Error statusResult of the last subroutine; 0 = success.UINT16Read/write0 = No errors; 1 = Sensor removed; 2 = No data in data log; 3 = Data log busy; 4 = Cannot update sensor calibration memory; 6 = Cannot perform this action; 7 = Sensor output too low; 8 = Sensor output too high; 9 = Power-up timeout active; 10 = Sensor/transmitter fault present; 11 = Autotest in progress; 12 = Input parameter too small; 13 = Input parameter too large; 14 = Cannot verify CPU memory; 15 = Alarm disabled, cannot change reset point; 16 = Not in fixed current output mode
HR2doc 40003Parameter data 016-bit subroutine parameter (integer or unsigned).UINT16Read/write
HR3doc 40004Parameter data 116-bit subroutine parameter (integer or unsigned).UINT16Read/write
HR4doc 40005Parameter data 216-bit subroutine parameter (integer or unsigned).UINT16Read/write
HR5doc 40006Parameter data 316-bit subroutine parameter (integer or unsigned).UINT16Read/write
HR6doc 40007Return data 016-bit subroutine return value.UINT16Read/write
HR7doc 40008Return data 116-bit subroutine return value.UINT16Read/write
HR8doc 40009Return data 216-bit subroutine return value.UINT16Read/write
HR9doc 40010Return data 316-bit subroutine return value.UINT16Read/write
HR10doc 40011Return data 416-bit subroutine return value.UINT16Read/write
HR11doc 40012Return data 516-bit subroutine return value.UINT16Read/write
HR12doc 40013Return data 616-bit subroutine return value.UINT16Read/write
HR13doc 40014Return data 716-bit subroutine return value.UINT16Read/write
HR32doc 40033Expanded faultsBITMAP16Readbit 0 = Factory calibration fault; bit 1 = Stack overflow
HR33doc 40034Expanded statusBITMAP16Readbit 0 = Gas generator installed; bit 1 = Gas generator type valid; bit 2 = Gas generator range valid; bit 3 = Alarm test active; bit 4 = Autotest in progress; bit 5 = Autotest pass; bit 6 = Cannot begin autotest; bit 7 = Autotest failed; bit 8 = Auto-clean active; bit 9 = Auto-clean recovering
HR34doc 40035FaultsBITMAP16Readbit 0 = Gas sensor ADC read fault; bit 1 = LCD bus fault; bit 2 = SPI bus fault; bit 3 = Temperature ADC read fault; bit 4 = Gas sensor input fault; bit 5 = Gas sensor removed; bit 6 = Gas sensor memory checksum fault; bit 7 = Gas sensor configuration fault; bit 8 = Gas generator removed; bit 9 = Gas generator configuration fault; bit 10 = System setup memory checksum fault; bit 11 = Alarm memory checksum fault; bit 12 = Operator interface memory checksum fault; bit 13 = HART memory checksum fault; bit 14 = Autotest failure; bit 15 = Relay jumper fitted but no relay voltage
HR35doc 40036StatusBITMAP16Readbit 0 = Caution active; bit 1 = Warning active; bit 2 = Alarm active; bit 3 = Fault active; bit 4 = CWAF inhibit active; bit 5 = Transmitter security active; bit 6 = System data log active; bit 7 = Current loop output fixed; bit 8 = Temperature input over range; bit 9 = Temperature input under range; bit 10 = Gas sensor input over range; bit 11 = Gas sensor input under range; bit 12 = Data log checksum error; bit 13 = Calibration history not initialised; bit 14 = Sensor in power-on delay
HR36doc 40037Gas concentrationUnblanked reading in the sensor's concentration units.FLOAT32CDABRead
HR38doc 40039Concentration % of full scaleUnblanked.FLOAT32CDAB%Read
HR40doc 40041TemperatureFLOAT32CDAB°CRead
HR42doc 40043Gas concentration (blanked)Sensor units, blanked around zero; the manual's main reading.FLOAT32CDABRead
HR44doc 40045Concentration % of full scale (blanked)FLOAT32CDAB%Read
HR46doc 40047Current loop outputLoop current derived from concentration.FLOAT32CDABmARead
HR48doc 40049Fixed loop currentLoop held at this value when above 0.0.FLOAT32CDABmARead
HR50doc 40051Loop DAC value10-bit DAC value behind the analog output.UINT16Read
HR51doc 40052Concentration 12-bit code0 = fault, 300 = inhibit, 800 = 0 %FS, 4000 = 100 %FS.UINT16Read
HR72doc 40073Sensor full-scale rangeConcentration that equals full scale.FLOAT32CDABRead
HR84doc 40085BlankingReadings within +/- this % of full scale show as zero.FLOAT32CDAB%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface

What Modbus registers does the Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface have?

This map lists 29 registers: 29 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual numbers holding registers 40001-40999 and states address = register number - 40001 (e.g. 40043 is sent as 42 / 0x2A).

What byte order does the Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface?

Start with HR 34 Faults (Fault bits); HR 35 Status (Status bits (caution/warning/alarm/fault)); HR 42 Gas concentration (blanked) (Gas concentration (blanked)); HR 38 Concentration % of full scale (Concentration % full scale); HR 40 Temperature (Temperature); HR 46 Current loop output (Loop current).

How do I enable Modbus control of the Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface?

Modbus is a factory-installed option. Set slave address on the transmitter at Menu > Setup > Modbus and baud/parity at Menu > Setup > System > Commun.

Where is the official Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface Modbus documentation?

The source is D12/F12 Series Modbus Interface O&M Manual (Rev G), revision 2007-08. Analytical Technology (ATI) doesn't publish it on its own website, so this map was re-typed from a free copy at https://loewener.dk/wp-content/uploads/2023/09/D12-F12-Modbus-Manual.pdf. It may be an older revision, so check it against the live unit.