- D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface
Sensor (gas transmitter / gas detector) · Modbus register map
Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface Modbus register map
Updated 17 November 2026
ATI's D12 (explosion-proof) and F12 (NEMA 4X) gas transmitters can carry a Modbus RTU option on RS-232 or RS-485. Everything sits in holding registers: a block at 40033-40052 gives fault and status words, gas concentration, temperature and loop current, and settings or calibrations are run by loading parameters and writing a subroutine number to 40001.
This page lists 29 Modbus registers for the Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Analytical Technology (ATI)’s own free documentation (linked below) and checked against it.
- Manufacturer
- Analytical Technology (ATI)
- Model
- D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface
- Equipment type
- Sensor (gas transmitter / gas detector)
- Registers
- 29 (14 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- D12, F12, D12 gas transmitter, F12 gas transmitter
Integration notes: Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface
Read holding registers 40035-40048 (address 34, 14 registers) in one FC03 request: faults, status, concentration, %FS, temperature and blanked readings, with floats low word first. Use subroutine 31 (with the alarm bits in 40003) to reset latched alarms.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 34 | Faults | BITMAP16 | Fault bits | Read |
| HR 35 | Status | BITMAP16 | Status bits (caution/warning/alarm/fault) | Read |
| HR 42 | Gas concentration (blanked) | FLOAT32 CDAB | Gas concentration (blanked) | Read |
| HR 38 | Concentration % of full scale | FLOAT32 CDAB | Concentration % full scale | Read |
| HR 40 | Temperature | FLOAT32 CDAB | Temperature | Read |
| HR 46 | Current loop output | FLOAT32 CDAB | Loop current | Read |
Enable Modbus control & writes
Modbus is a factory-installed option. Set slave address on the transmitter at Menu > Setup > Modbus and baud/parity at Menu > Setup > System > Commun.
Byte order & addressing
- Floats and longs are CDAB.
- FC01/02/04 return zeros rather than exceptions.
- Report Slave ID returns 1100.
Network setup
- Defaults: address 1, 9600 baud, N,8,1.
- Baud can be 300-28.8k; parity options N81, N82, E81, O81.
Watch out for
- The transmitter answers within about 250 ms, so poll no faster than about 3 times a second.
- D12 units with IR sensors use a different register table.
Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Subroutine select | Write a subroutine number to run it, after loading parameters into 40003-40006. | UINT16 | Read/write | 10 = Zero sensor; 11 = Span sensor; 12 = Get calibration history info; 13 = Get calibration record; 14 = Change sensor range; 15 = Change sensor damping; 16 = Change sensor blanking; 17 = Change autotest state; 18 = Calibrate temperature reading; 20 = Change alarm set point; 21 = Change alarm reset point; 22 = Change alarm set delay; 23 = Change alarm reset delay; 27 = Change alarm options; 28 = Change relay configuration; 29 = Change inhibit timeout period; 30 = Change alarm inhibit state; 31 = Reset alarms; 32 = Start alarm relay test; 33 = Stop alarm relay test; 40 = Change inhibit mA level; 41 = Change fault mA level; 42 = Change autotest mA level; 47 = Force mA output; 48 = Correct 4 mA level; 49 = Correct 20 mA level; 50 = Change lock status; 51 = Change password; 60 = Change system clock; 61 = Input keycode; 70 = Change datalog state; 71 = Change datalog sampling rate; 72 = Get datalog info; 73 = Get datalog record; 100 = Convert concentration real to %FS integer; 101 = Convert %FS integer to real | |||
| HR | 1doc 40002 | Error status | Result of the last subroutine; 0 = success. | UINT16 | Read/write | 0 = No errors; 1 = Sensor removed; 2 = No data in data log; 3 = Data log busy; 4 = Cannot update sensor calibration memory; 6 = Cannot perform this action; 7 = Sensor output too low; 8 = Sensor output too high; 9 = Power-up timeout active; 10 = Sensor/transmitter fault present; 11 = Autotest in progress; 12 = Input parameter too small; 13 = Input parameter too large; 14 = Cannot verify CPU memory; 15 = Alarm disabled, cannot change reset point; 16 = Not in fixed current output mode | |||
| HR | 2doc 40003 | Parameter data 0 | 16-bit subroutine parameter (integer or unsigned). | UINT16 | Read/write | ||||
| HR | 3doc 40004 | Parameter data 1 | 16-bit subroutine parameter (integer or unsigned). | UINT16 | Read/write | ||||
| HR | 4doc 40005 | Parameter data 2 | 16-bit subroutine parameter (integer or unsigned). | UINT16 | Read/write | ||||
| HR | 5doc 40006 | Parameter data 3 | 16-bit subroutine parameter (integer or unsigned). | UINT16 | Read/write | ||||
| HR | 6doc 40007 | Return data 0 | 16-bit subroutine return value. | UINT16 | Read/write | ||||
| HR | 7doc 40008 | Return data 1 | 16-bit subroutine return value. | UINT16 | Read/write | ||||
| HR | 8doc 40009 | Return data 2 | 16-bit subroutine return value. | UINT16 | Read/write | ||||
| HR | 9doc 40010 | Return data 3 | 16-bit subroutine return value. | UINT16 | Read/write | ||||
| HR | 10doc 40011 | Return data 4 | 16-bit subroutine return value. | UINT16 | Read/write | ||||
| HR | 11doc 40012 | Return data 5 | 16-bit subroutine return value. | UINT16 | Read/write | ||||
| HR | 12doc 40013 | Return data 6 | 16-bit subroutine return value. | UINT16 | Read/write | ||||
| HR | 13doc 40014 | Return data 7 | 16-bit subroutine return value. | UINT16 | Read/write | ||||
| HR | 32doc 40033 | Expanded faults | BITMAP16 | Read | bit 0 = Factory calibration fault; bit 1 = Stack overflow | ||||
| HR | 33doc 40034 | Expanded status | BITMAP16 | Read | bit 0 = Gas generator installed; bit 1 = Gas generator type valid; bit 2 = Gas generator range valid; bit 3 = Alarm test active; bit 4 = Autotest in progress; bit 5 = Autotest pass; bit 6 = Cannot begin autotest; bit 7 = Autotest failed; bit 8 = Auto-clean active; bit 9 = Auto-clean recovering | ||||
| HR | 34doc 40035 | Faults | BITMAP16 | Read | bit 0 = Gas sensor ADC read fault; bit 1 = LCD bus fault; bit 2 = SPI bus fault; bit 3 = Temperature ADC read fault; bit 4 = Gas sensor input fault; bit 5 = Gas sensor removed; bit 6 = Gas sensor memory checksum fault; bit 7 = Gas sensor configuration fault; bit 8 = Gas generator removed; bit 9 = Gas generator configuration fault; bit 10 = System setup memory checksum fault; bit 11 = Alarm memory checksum fault; bit 12 = Operator interface memory checksum fault; bit 13 = HART memory checksum fault; bit 14 = Autotest failure; bit 15 = Relay jumper fitted but no relay voltage | ||||
| HR | 35doc 40036 | Status | BITMAP16 | Read | bit 0 = Caution active; bit 1 = Warning active; bit 2 = Alarm active; bit 3 = Fault active; bit 4 = CWAF inhibit active; bit 5 = Transmitter security active; bit 6 = System data log active; bit 7 = Current loop output fixed; bit 8 = Temperature input over range; bit 9 = Temperature input under range; bit 10 = Gas sensor input over range; bit 11 = Gas sensor input under range; bit 12 = Data log checksum error; bit 13 = Calibration history not initialised; bit 14 = Sensor in power-on delay | ||||
| HR | 36doc 40037 | Gas concentration | Unblanked reading in the sensor's concentration units. | FLOAT32 | CDAB | Read | |||
| HR | 38doc 40039 | Concentration % of full scale | Unblanked. | FLOAT32 | CDAB | % | Read | ||
| HR | 40doc 40041 | Temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 42doc 40043 | Gas concentration (blanked) | Sensor units, blanked around zero; the manual's main reading. | FLOAT32 | CDAB | Read | |||
| HR | 44doc 40045 | Concentration % of full scale (blanked) | FLOAT32 | CDAB | % | Read | |||
| HR | 46doc 40047 | Current loop output | Loop current derived from concentration. | FLOAT32 | CDAB | mA | Read | ||
| HR | 48doc 40049 | Fixed loop current | Loop held at this value when above 0.0. | FLOAT32 | CDAB | mA | Read | ||
| HR | 50doc 40051 | Loop DAC value | 10-bit DAC value behind the analog output. | UINT16 | Read | ||||
| HR | 51doc 40052 | Concentration 12-bit code | 0 = fault, 300 = inhibit, 800 = 0 %FS, 4000 = 100 %FS. | UINT16 | Read | ||||
| HR | 72doc 40073 | Sensor full-scale range | Concentration that equals full scale. | FLOAT32 | CDAB | Read | |||
| HR | 84doc 40085 | Blanking | Readings within +/- this % of full scale show as zero. | FLOAT32 | CDAB | % | Read |
Notes on this map
- Source is a copy hosted by the Danish distributor Loewener; ATI does not host this Modbus manual publicly as far as two searches showed. It is the unaltered ATI document (Rev G, Aug 2007).
- 32-bit values (REAL and LONG) are low word first (CDAB): the manual's example puts 0x4000 in 40003 and 0x459C in 40004 for 5000.0, and says only the register order, not the bytes, has to be swapped.
- Only registers 40001-40014 can be written; writing above 40014 returns exception 02. Settings and calibrations are changed through subroutines: load 40003-40006 (a float parameter fills two of them, low word first), write the number to 40001, then read 40002 for the result.
- The table lists 'LDATA' long parameters as type REAL, which conflicts with their name; they are left out. The raw ADC registers 40053-40069, gain/offset internals 40071-40083 (except range 40073), and the internal ADC words 40088 on are also left out.
- The manual's own table header for 40015 (listen-only) gives no value coding, so it is not listed.
- Concentration units depend on the fitted sensor (ppm, %LEL and so on); the transmitter shows them on its display.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface
What Modbus registers does the Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface have?
This map lists 29 registers: 29 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual numbers holding registers 40001-40999 and states address = register number - 40001 (e.g. 40043 is sent as 42 / 0x2A).
What byte order does the Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface?
Start with HR 34 Faults (Fault bits); HR 35 Status (Status bits (caution/warning/alarm/fault)); HR 42 Gas concentration (blanked) (Gas concentration (blanked)); HR 38 Concentration % of full scale (Concentration % full scale); HR 40 Temperature (Temperature); HR 46 Current loop output (Loop current).
How do I enable Modbus control of the Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface?
Modbus is a factory-installed option. Set slave address on the transmitter at Menu > Setup > Modbus and baud/parity at Menu > Setup > System > Commun.
Where is the official Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface Modbus documentation?
The source is D12/F12 Series Modbus Interface O&M Manual (Rev G), revision 2007-08. Analytical Technology (ATI) doesn't publish it on its own website, so this map was re-typed from a free copy at https://loewener.dk/wp-content/uploads/2023/09/D12-F12-Modbus-Manual.pdf. It may be an older revision, so check it against the live unit.
Other gas detectors register maps
- Sensor (extractive gas detector)
New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP)
New Cosmos PS-8 series pump-type gas detectors for semiconductor plants (up to 16 sensor channels) with Ethernet Modbus TCP, Instruction Manual for Communication GAE-180-00 (December 2024).
Also known as: PS-8, PS-8 series, New Cosmos PS-8 - Sensor (fixed gas detector)
Teledyne Detcon Model FP-700 catalytic bead combustible gas sensor (RS-485 Modbus)
Teledyne Detcon FP-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3168, Rev. 5.7.
Also known as: FP-700, Detcon FP-700, Teledyne Detcon FP-700 - Sensor (water leak detector)
Teracom TSF400-4 water-leak detector with Modbus RTU
TSF400-4 per the Teracom TSF400-4 user manual Revision R1.2.
Also known as: TSF400-4 - Sensor (extractive gas detector)
Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)
Honeywell Midas S2 single-point extractive gas transmitters with Ethernet/PoE, user manual 3023M5001 Rev A, Modbus/TCP register map (Table 6-1).
Also known as: Midas S2, MIDAS-S2, Midas S2 gas detector - Sensor (fixed gas detector)
Teledyne Detcon Model DM-700 electrochemical toxic gas / oxygen sensor (RS-485 Modbus)
Teledyne Detcon DM-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3207, Rev. 5.9.
Also known as: DM-700, Detcon DM-700, Teledyne Detcon DM-700 - Sensor (fixed gas detector)
Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)
Teledyne Oldham Simtronics OLCT 700 and OLCT 710 FP detectors with 4-20 mA and RS-485 Modbus RTU, manual NP700FPIMEN Revision E.0.
Also known as: OLCT 700 FP, OLCT 710 FP, Oldham OLCT 700 FP, 700 FP series
All gas detectors Modbus register maps →