Manufacturer
ICP DAS Modbus register maps
Updated 19 November 2026
4 ICP DAS models, 220 registers in all, each re-typed from ICP DAS’s own free documentation and checked against it.
- Sensor (thermistor input module)
ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)
M-7005 in Modbus RTU mode, per I-7005/M-7005 User Manual Rev B2.4 (7MH-018-B24). The I-7005 uses the DCON protocol and is not covered.
Also known as: M-7005, M7005, I-7005/M-7005 - Sensor (counter/frequency input module)
ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)
ICP DAS M-7080 and M-7080B two-channel 32-bit counter/frequency modules with two digital outputs, in Modbus RTU mode.
Also known as: M-7080, M-7080B, M7080, M7080B - Sensor (PWM output and counter input module)
ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU)
ICP DAS M-7088 eight-channel PWM output module with eight digital inputs and counters, Modbus RTU firmware.
Also known as: M-7088, M7088 - Sensor / remote digital I/O module
ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)
tM-P4C4 (4 DI + 4 DO), tM-C8 (8 DO) and tM-P8 (8 DI) with the Modbus RTU protocol selected, per the tM Series DIO User Manual Rev A1.4.
Also known as: tM-P4C4, tM-C8, tM-P8
ICP DAS: default communication settings
Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).
| Model | Transport | Unit ID | Serial | Word order | Documented addressing | Registers |
|---|---|---|---|---|---|---|
| M-7005 8-channel thermistor input module (Modbus RTU) | RTU | Not stated | 8N1 | 16-bit only | Modicon | 22 |
| M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) | RTU | Not stated | - | CDAB | Modicon | 24 |
| M-7088 8-channel PWM output / counter input module (Modbus RTU) | RTU | 1 | 9600 baud, 8N1 | CDAB | Modicon | 80 |
| tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) | RTU/ASCII | 1 | 9600 baud | 16-bit only | Modicon | 94 |